Tender notice
Main LV to Sub Main Feed Cable Replacement
Notice details
- Published
- Category
- works
- Buyer region
- East of England
- Source
- View official notice
Public buyer
Tender value£600,000
- Planned startAs published in the notice
- Planned endAs published in the notice
Work description
The existing cables are over 20 years old and have been subject to degradation due temperature variations through power loading and the local environment, currently the feed cable to FCS sub main panel failed an insulation resistance test with a reading of 800K Ohms, this reading fluctuates between 800k Ohms and 1.2 M Ohms . The pass level is 1 M-Ohm, we are experiencing these readings on testing other main feed cables, so a programme of replacement is required.